Please register the attached report
and email below as an application to discharge conditions on planning permission
2009/1943/P.
I have already advised them that a
fee of £85 is required.
Thanks
Max
Smith
Telephone:
020 7974 5114
From: DE Ops South-LMS13e (Spalding
Louise Ms) [mailto:Louise.Spalding@de.mod.uk]
Sent: 25 August 2009 10:40
To:
Cc: DE Ops
South-LMS13c (Allan Peter Mr)
Subject: RE: St Georges Court 2 - 12
Bloomsbury Way London WC1H 8BB, Planning consultation 2009/1943/P; Discharge of
planning conditions 2 and 3
Dear
Max
I write to ask you to
formally discharge conditions 2 and 3 of the above application in accordance
with the decision letter dated 3
July 2009.
For your
information I enclose another copy of our noise report which contains
the information required in order to discharge the
conditions.
If you require any
further information or wish to discuss please contact me. My mobile number
is 07970 403323.
Regards
Louise
Spalding
Defence
Estates
From:
Sent: 29 July 2009 18:48
To: DE Ops South-LMS13e (Spalding Louise
Ms)
Subject: RE: St Georges
Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning consultation
2009/1943/P
Louise
The decision notice has been posted
online at
Regards
Max
Smith
Telephone:
020 7974 5114
From: DE Ops South-LMS13e (Spalding
Louise Ms) [mailto:Louise.Spalding@de.mod.uk]
Sent: 29 July 2009 15:13
To:
Subject:
RE: St Georges Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning
consultation 2009/1943/P
Dear
Max
I have not yet received
the decision notice on the above planning application. We are keen to get
the noise condition discharged. Could you please fax the decision letter
to Peter Allan, so that I can formally ask you to discharge the
relevant condition. I will attach another copy of the noise
report with the letter.
Our fax number is 0207
305 4175.
Regards
Louise Spalding
07970
403323
From:
Sent: 27 July 2009 15:58
To: DE Ops South-LMS13e (Spalding Louise
Ms)
Subject: RE: St Georges
Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning consultation
2009/1943/P
Louise
I’m sorry to hear that.
According to our records, the letter
was sent on the 3rd July. However, we have been afflicted by postal
strikes lately. I will arrange for a copy to be
sent.
Regards
Max
Smith
Telephone:
020 7974 5114
From: DE Ops South-LMS13e (Spalding
Louise Ms) [mailto:Louise.Spalding@de.mod.uk]
Sent: 27 July 2009 14:47
To:
Cc: DE Ops
South-LMS13c (Allan Peter Mr)
Subject: St Georges Court 2 - 12 Bloomsbury
Way London WC1H 8BB, Planning consultation 2009/1943/P
Dear
Max
Further to your e-mail
of 6 July, I have not yet received the decision notice. I assume it
is on its way. Perhaps you could let me know when I might receive
it.
Regards
Louise
Spalding
07970
403323
From:
Sent: 06 July 2009 10:47
To: DE Ops South-LMS13e (Spalding Louise
Ms)
Subject: RE: St Georges
Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning consultation
2009/1943/P
Louise
Planning permission with an
appropriate condition has now been granted. The decision notice is on its way to
you.
Regards
Max
Smith
Telephone:
020 7974 5114
From: DE Ops South-LMS13e (Spalding
Louise Ms) [mailto:Louise.Spalding@de.mod.uk]
Sent: 03 July 2009 11:59
To:
Subject:
RE: St Georges Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning
consultation 2009/1943/P
Max
I have spoken to John
Anani this morning who has, I understand agreed with you that he will
recommend to you to condition the application's
approval.
Further I understand
that you will now be approving the application with this
condition.
I would be grateful if
you could confirm this and I look forward to hearing from
you.
I have already told you
that the sound recording is going ahead this weekend in accordance with John's
requirements and I expect to get the report to you and John on Tuesday of next
week.
Please contact me if
you require any further clarification.
Regards
Louise
Spalding
07970
403323
From:
Sent: 09 June 2009 16:12
To: DE Ops South-LMS13e (Spalding Louise
Ms)
Subject: FW: St Georges
Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning consultation
2009/1943/P
Dear
Louise
Our Environmental
Health Officer noted the following:
2.
The noise level measured on the roof at midday in October 2008 was 49dBA. This
implies that a Chiller was running when the background noise level was
measured.
3.
In another document titled “The replacement of chillers in
The following is
therefore requested:
2.
The acoustic report shall include measured background noise with all existing
items of plant on the roof switched off.
3.
The acoustic report shall demonstrate theoretically, with spreadsheet
calculations, that
4.
The nearest resident shall be indentified in the acoustic report with a location
map.
I would be grateful
if you provide this information within 14 days of this email, otherwise the
application will be determined on it's current
merits.
Regards
Max…
Max
Smith
Senior Planning Officer
Development Control
Planning Services
London Borough
of Camden
Tel: 020 7974 5114
Fax: 020 7974 1680
www.camden.gov.uk/planning
Town Hall Extension
Argyle
Street
This e-mail is intended solely for the person to whom
it is addressed. It may contain confidential or privileged information. If you
receive this message but are not the intended recipient you are expressly
notified that any copying or dissemination of this message without our
permission is prohibited. You must not copy, distribute or take any action in
reliance on it. Unless stated to the contrary, any opinions or comments are
personal to the writer and do not represent the official view of the Council.
______________________________________________
From:
Anani, John
Sent:
08
June 2009 16:46
To:
Subject:
St
Georges Court 2 - 12 Bloomsbury Way London WC1H 8BB, Planning consultation
2009/1943/P
Dear Max
I refer to the
above application for the replacement of two existing Chiller units with two new
chillers units on roof of offices (Class B1). Having read through the docs in
support of the application, I note the following:
2.
The noise level measured on the roof at midday in October 2008 was 49dBA. This
implies that a Chiller was running when the background noise level was
measured.
3.
In another document titled “The replacement of chillers in
4.
Also that the new plant will be enclosed with acoustic
louvres.
With this scattered information, I
am inclined to request for the following:
2. The
acoustic report shall include measured background noise with all existing items
of plant on the roof switched off.
3. The
acoustic report shall demonstrate theoretically, with spreadsheet calculations,
that
4. The
nearest resident shall be indentified in the acoustic report with a location
map.
Please revert to me with any
queries.
Best wishes
John
Dr John
Anani
Senior Technical Officer
Compliance & Enforcement
Team
Regulatory
Services
Culture and Environment
Directorate
Tel:
020 7974 2652
Fax: 020 7974 6955
E-mail:
john.anani@camden.gov.uk
This e-mail may contain information which is
confidential, legally privileged and/or copyright protected. This e-mail is
intended for the addressee only. If you receive this in error, please contact
the sender and delete the material from your
computer
This e-mail may contain information which is
confidential, legally privileged and/or copyright protected. This e-mail is
intended for the addressee only. If you receive this in error, please contact
the sender and delete the material from your
computer
This e-mail may contain information which is
confidential, legally privileged and/or copyright protected. This e-mail is
intended for the addressee only. If you receive this in error, please contact
the sender and delete the material from your
computer
This e-mail may contain information which is
confidential, legally privileged and/or copyright protected. This e-mail is
intended for the addressee only. If you receive this in error, please contact
the sender and delete the material from your
computer